Fire!

Table of contents

How safe is your vessel or workplace?

detail of a falla valenciana burning between flame 2024 10 21 06 07 25 utc

Following on from last week’s newsletter regarding Emergency Preparedness and Procedures – we wanted to take a closer look at an AMSA case more closely for the lessons learned.

A commercial fishing vessel was on a voyage in Queensland when the master noticed an auxiliary engine alarm. Upon lifting the engine room hatch, the master saw smoke and an orange glow and the engine room subsequently caught fire. The master quickly made the decision that they would not be able to fight the fire without jeopardising their safety and abandoned ship. An SMS risk assessment on appropriate crewing on a voyage greater than 12 hours duration should be undertaken in these situations.

What happened?

A Class 3B commercial fishing vessel, on voyage, when the master, being the only one onboard, became alarmed by a change in engine sound. Moments later, they noticed alarms for the auxiliary engine were activated on the panel at the helm position. The master left the helm position to check the machinery and engine room, leaving the engine in gear. The master opened the engine hatch and discovered smoke and a glowing orange colour in the engine room. They returned to the helm to disengage the main engine & on turning back, saw flames coming from the engine hatch. The master made a rapid decision not to fight the fire as they risked entrapment if they could not get past the fire to the vessels aft where a tender was secured. The master went aft and boarded the tender. The tender was momentarily caught under the back of the vessel and the master fell partially into the water. The master freed the tender and moved away from the vessel. The vessel burned to the waterline and subsequently sank. No injuries were reported. 

Investigation findings

The investigation identified the following contributory factors:

  • The master inadvertently introduced oxygen to an accelerating fuel and heat situation and the engine room caught fire. It is believed the fire started at the auxiliary engine.
  • The master made the quick and safe decision not to fight the fire in case they were trapped and could not abandon ship safely via the attached tender at the vessels aft.
  • The vessel, built in approximately 1990 and not in survey, was not fitted with a fire suppression system in the engine room and the fire emergency air vents and fuel shut off system were not activated.
  • The vessel was undertaking a voyage of greater than 12 hours duration as a single person operation. DCV crew that are awake for greater than 12 hours during a voyage have reported high levels of fatigue.

Lessons Learned

1.         Training is essential. 
The Master should have automatically known to close the engine hatch to avoid introducing oxygen and accelerating the situation. 
The Master did show knowledge, by making the prompt decision to Abandon Ship and follow appropriate procedures.

2.         Check Equipment / Maintain Frequently
It appears the vessel was not fitted with a fire suppression system in the Engine Room, and whilst not required, would have saved the vessel in this case, so we encourage you to rethink and ensure all equipment, especially safety is installed and maintained.

3.         Procedures are up-to-date and inducted regularly

The Fire Emergency Air Vents nor the fuel shut off system were activated showing that procedures where either not followed, not updated or even not written!

4.         Fatigue Risk Management Plan

It is now law, that EVERY commercial vessel holds a Fatigue Risk Management Plan to ensure the safety and wellbeing of the vessel and crew.  Whilst we are unsure in this case of the Masters fatigue levels, we should all be aware of Fatigue, it’s dangers and ensuring you have a plan to cover all scenarios.

Over the last 12 months we’ve undertaken several Safety Audits both on vessels and in workplaces ashore and conducted multiple onboard training sessions where fire safety was compromised.

How does your fire safety stack up?

Here’s a short list of things we’ve discovered during our Safety Audits and training sessions:

  • Empty fire extinguishers
  • Fire extinguishers not serviced
  • In one case the engine room fire suppression system bottle was empty
  • Air shut offs not functioning. Often these had been painted over during refit
  • Air shut offs with damaged dampeners
  • In another case an air shut off that had a bolt from a fitting located in the vent pipe which prevented the dampener from closing
  • Inoperable fuel shut offs
  • In one case a fuel shut off that had to be accessed through a hole in the deck with a fitting that could not be removed
  • Fire hydrants and/or hoses in disrepair
  • A lack of knowledge on how to deal with a fire, even a minor one!

All of the above put the vessels at risk in the event of a fire onboard, especially in the engine room.

While the above list is based on vessels many of the items are also relevant to workplaces such as factories, offices, etc.

Fire extinguishers that have been discharged or otherwise become inoperable should never be onboard or in the workplace, they must be serviced when due.

image 4

Check the gauge on a regular basis and if it is in the RECHARGE section, get it recharged immediately!

Do you have Dry Chemical extinguishers on your vessel in your workplace? If yes ensure you know what class they are as there are two classes for Dry Chemical extinguishers, these are:

ABE Type :

  • Class A Fires – paper, cardboard, wood, fabrics, people etc.
  • Class B Fires – flammable liquid fires, petrol, diesel, oil etc
  • Class E Fires – electrical fires, computers, photocopiers, switchboards etc

BE Type:

  • Class B Fires – flammable liquid fires, petrol, diesel, oil etc
  • Class E Fires – electrical fires, computers, photocopiers, switchboards etc

Air shut offs that do not fully operate put your vessel at risk. You need to check them for full operation regularly, especially after a refit where painting has been undertaken.

The picture below was supplied by AMSA as an example of a damaged air dampener.

image 5

Fuel Shut offs: The location and operation of your fuel shut offs is also critical for your safety in the event of an engine room fire. These should also be checked regularly for effective operation.

The picture below is an example of a cable operated fuel shut off.

Fire hydrants and fire hoses are fitted on many vessels, but we’ve found ‘lay flats” hoses that were in disrepair, one that even feel apart when pulled out!

image 6

Shorlink’s Recommendation

For your safety and the safety of your crew, workers and/or clients and vessel or premises ensure you have a procedure in place and that you undertake regular drills.

Secondly make sure all crew and workers can identify the classes of extinguishers and their specific uses.

Also, it’s critical to your safety that you undertake regular checks of ALL your firefighting apparatus and equipment to ensure it works when required.


Tip

Training, Training, Training! Whether you complete the training and inductions yourself or engage Shorlink to complete on your behalf – training does truly save lives. Ensure your training and inductions are up-to-date and the necessary forms have been completed in your SMS.

If you have any questions or doubts, please feel free to reach out to us on (07) 4242 1412.

Subscribe to our newsletter

social
Shorlink logo
  • Australia-wide support
    Mon to Fri - 9am to 5pm
  • Call: +61 (7) 4242 1412
  • Email: contact@shorlink.com
  • PO Box 3086,
    Bracken Ridge, Qld 4017
Shorlink Pty Ltd acknowledges Aboriginal and Torres Strait Islander Peoples as the Traditional Custodians of land, sea and sky, recognising their deep, enduring connection to these places. We pay our respects to Elders past and present who hold the knowledge, culture and spiritual connections to land, sky and waters and whose guidance continues to shape their sustainable, ethical and responsible care.
© 2026 Shorlink Pty Ltd. All Rights Reserved.
ABN 61 118 083 006 / Private Investigator Licence No: 4924789 / Certified Drug and Alcohol Collector ID No: OD-004630
[Managed] Web Solutions
Your subscription could not be saved. Please try again.
Your Shorlink Newsletter subscription has been successful.

Subscribe to Shorlink Newsletter